Mitsubishi Electric CITY MULTI P250YMF-B Instrukcja Instalacji

Przeglądaj online lub pobierz Instrukcja Instalacji dla Klimatyzatory typu split Mitsubishi Electric CITY MULTI P250YMF-B. Mitsubishi Electric CITY MULTI P250YMF-B Installation manual Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj

Podsumowanie treści

Strona 1 - Service Handbook

AIR CONDITIONERS CITY MULTI Series Y, Super YService HandbookModels PUHY-400YMF-B, 500YMF-BPUHY-P400YMF-B, P500YMF-BPUHY-600YSMF-B, 650YSMF-B, 700YSMF

Strona 2 - Contents

–7–[7] Charging of RefrigerantR407C must be in a liquid state when charging, because it is a non-azeotropic refrigerant.For a cylinder with a syphon a

Strona 3 - Safety precautions

–97–ItemAt compressor is startedAfter thermostat reset or 3minutes after startupCompressor stopped duringcooling or heating modeAfter operation has be

Strona 4

–98–(5) Oil return control (Electronic expansion valve (SLEV); Variable Capacity Unit only)• The amount of opening of the oil-return LEV (SLEV) is det

Strona 5

–99–5) Change in number of operating indoor units while defrosting• If the number of indoor units changes while the outdoor unit is defrosting, the de

Strona 6 - [2] Piping Machining

–100–(10) Liquid Distribution Control (electronic expansion valve (LEV2) constant capacity unit only)• Liquid distribution control refers to the proce

Strona 7

–101–(11) Liquid Refrigerant Correction ControlThe liquid refrigerant correction control adjusts the liquid refrigerant amounts between both accumulat

Strona 8 - [4] Brazing

–102–(12) Refrigerant recovery controlRefrigerant recovery is conducted to prevent refrigerant from accumulating in the stopped unit (fan unit), the u

Strona 9 - [6] Vacuuming

–103–(14) Control at initial starting• When the ambient temperature is low (5°C or less in cooling and – 5°C or less in heating), initial starting wil

Strona 10 - [8] Dryer

–104–<Initial Start Control Timingchart>For steps 1 - 3Note 1: If the frequency of No. 1 compressor is above the specified level at the end of S

Strona 11 - 2 COMPONENT OF EQUIPMENT

–105–For steps 4 - 6(Example 1)A-minuteStep 4 Step 5 Step 610minutes5minutesON/OFF of No.1 compressorON/OFF of No.2 compressorON/OFF of No.3 compresso

Strona 12 - Controller Box

–106–Note 1: If Step 4 is interrupted (compressor stopped by thermostat OFF or regular stop), Step 4 will be redone atrestart.Note 2: If Step 5 is int

Strona 13 - Noise Filter Box

–8–22222 COMPONENT OF EQUIPMENT[1] Appearance of Components1 Variable capacity unitRearAmbient temperature SensorHeat ExchangerAccumulatorHeat Exchang

Strona 14 - MAIN board

–107–(17) Emergency response operating modeThe emergency operation mode is a mode in which the unit is run in an emergency to respond to the trouble w

Strona 15 - INV board

–108–2) Terminating Emergency Response Operation Mode(Termination Conditions)When one of the following conditions is met, emergency operation mode is

Strona 16 - FANCON board

–109–[2] Operation Flow Chart(1) Outdoor unit (Cooling, heating modes)Note: 1 For about 2 minutes after turning on power source, address and group inf

Strona 17 - RELAY board

–110–(2) Indoor unit (Cooling, heating, dry, and fan modes)Note: 1 At indoor unit LEV full closed, the opening angle indicates 60.Note: 2 The error mo

Strona 18 - Heat exchanger

–111–YESNOYESYESYESNONO(3) Cooling operationNormal operationsTest runStopCooling operation4-way valve OFFIndoor unit fanoperationsTest run startThermo

Strona 19

–112–(4) Heating operationNote: 1 When the outdoor unit goes into defrost operations, a defrost operation command is sent to the indoor unit.Once the

Strona 20 - CONT board

–113–(5) Dry operationNote: 1 When indoor unit inlet temperature exceeds 18°C, outdoor unit (compressor) and indoor unit fan start intermittent operat

Strona 21 - 1 PUHY-P400·500YMF-B

–114–1 Adjustment of super heat of heat ex-changer outlet port of indoor unitduring cooling.2 Adjustment of sub-cool of heat ex-changer outlet port of

Strona 22 - 2 PUHY-400·500YMF-B

–115–1 Detects the outdoor air temperature.2 Performs fan control, liquid levelheater control, opening settings ofLEV for oil return and other functio

Strona 23 - 3 PUHY-P600·650·700·750YSMF-B

–116–Resistance checkResistance checkConductivity checkusing tester.Conductivity checkusing tester.Conductivity checkResistance checkResistance checkB

Strona 24 - PUHY-200,250YMF-B

–9–Controller BoxRELAY boardFANCON boardMAIN board INV boardChoke coil (L2)Magnetic contactor(52C2)Magnetic contactor(52F)Transistor module(TRM)Therma

Strona 25 - [3] Equipment Composition

–117–SV1Discharge –Suction BypassSV2capacitycontrol (fullload)SV3capacitycontrol(unload)SV4Discharge –Suction BypassSV5bLiquid pipesLEV1(SC coil)LEV2C

Strona 26

–118–[4] Resistance of Temperature SensorThermistor for low temperatureThermistor R0 = 15 kΩ ± 3 % (TH3 ~ 9a, 9b,10a,10b) Thermistor R120 = 7.465 kΩ ±

Strona 27 - [4] Electrical Wiring Diagram

–119–66666 REFRIGERANT AMOUNT ADJUSTMENTBy clarifying the relationship between the refrigerant amount and operating characteristics for Super Y Series

Strona 28 - <Internal layout>

–120–(2) Refrigerant Volume1) Checking the Operating ConditionOperate all the indoor units on cooling or on heating, checking the discharge temperatur

Strona 29

–121–(3) Additional Refrigerant Charge VolumeAt the time of shipping from the factory, the outdoor unit is charged with the amount of refrigerant show

Strona 30 - [5] Standard Operation Data

–122–[3] Refrigerant Volume Adjustment Mode Operation(1) ProcedureDepending on the operating conditions, it may be necessary either to charge with sup

Strona 31

–123–Caution:Do not let the drained out refrigerant escape to the outside atmosphere.• Always be sure to charge with refrigerant from the liquid phase

Strona 32

–124–PUHY-(P) 600·650·700·750 YSMF-BOver 6 minutes have passed since variable andconstant capacity unit startup.AL1 and AL2 are0 or 1.Start adjustment

Strona 33

–125–(3) Refrigerant adjustment in heating season (Flow chart)PUHY-(P) 400·500 YMF-BStartAdjustmentHas the operating condition stabilized?Is the accum

Strona 34

–126–PUHY-(P) 600·650·700·750 YSMF-BYESNOStart AdjustmentAdjustment completedRun all the indoor units in theheating condition in the testrun mode.Has

Strona 35

–10–Noise filter (NF)DC reactor (DCL)Noise filter boxNoise Filter Box(Rear of the controller box)

Strona 36 - 2 Heating operation

–127–Note: 1 If there are any units which are not operating, it will cause refrigerant to accumulate, so by all means operate all theindoor units. Als

Strona 37

–128–(4) R22 Gauge pressure - saturation temperature conversion chartPressure→↓0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.91 – 25.2 – 24.0 – 22.8 – 21.7 – 20

Strona 38

–129–77777 TROUBLESHOOTING[1] Principal Parts(1) Judging FailurePressure Sensor (Discharge/Suction Pressure Sensor)1) Check for failure by comparing t

Strona 39

–130–• Connector connection specifications on the pressure sensor body side.The connector’s pin numbers on the pressure sensor body side differ from t

Strona 40

–131–5) SV6When No. 2 compressor is operating and No. 2 compressor is stopped, the main SV6 will be set to ON, making itpossible to confirm operation

Strona 41

–132–2) SV2, 3 (Full-load / Un-load switching valve) PUHN-P-YMF-B only1 It starts in un-load in the initial start mode and during defrosting, and star

Strona 42

–133–Outdoor LEVThe valve opening angle changes in proportion to the number of pulses.(Connections between the outdoor unit’s MAIN board and SLEV, LEV

Strona 43 - 2 Constant Capacity Unit

–134–2 LEV2Pulse Signal Output and Valve OperationOutput (Phase) Output StateNo. 1 2 3 4ø1 ON OFF OFF ONø2 ON ON OFF OFFø3 OFF ON ON OFFø4 OFF OFF ON

Strona 44

–135–IndoorOutdoorIndoorOutdoorIndoorOutdoorIndoorIndoorOutdoorFailure Mode Judgment Method Treatment Affected LEVMicrocomputerDriver CircuitFailureLE

Strona 45

–136–Outdoor LEV (SLEV, LEV1) Coil Removal Procedure (configuration)As shown in the figure, the outdoor LEV is made in such a way that the coils and t

Strona 46 - Cooling capacity saving

–11–MAIN boardCNTR CNFC1CNVCC4Power source forcontrolCNS1M-NETtransmissionCNS2M-NETtransmis-sion(Centralizedcontrol)CN40M-NET transmissionpower supply

Strona 47

–137–Power transistorMeasure resistances between each terminal of transistor module with tester, and use the results for troubleshooting.Specified res

Strona 48 - 3 TEST RUN

–138–Thyristor module (SCRM)<Judgment Method> Measure the resistance between each of the SCRM pins and judge if there is a failure or not bythe

Strona 49 - Insulation pipe

–139–12*1 Check the transformer in accordance with the “TROUBLE SHOOTING” in the indoor unit’s service handbook.Symptom Cause Checking method & co

Strona 50

–140–Symptom Cause3(Without using MELANS)1) Outdoor unit address is set to “000.”2) Erroneous address.1 Address setting miss of indoor unit to be coup

Strona 51

–141–Symptom Cause Checking method & countermeasure“88” appears on re-mote controller at theregistration and accessremote controller4 [Generates a

Strona 52

–142–Transmission Power Circuit (30 V) Check ProcedureIf “ ” is not displayed by the remote control, investigate the points of the trouble by the fo

Strona 53

–143–(3) Investigation of transmission wave shape/noiseControl is performed by exchanging signals between outdoor unit, indoor unit and remote control

Strona 54

–144–3) Checking and measures to be taken(a) Measures against noiseCheck the items below when noise can be confirmed on wave shape or the error code i

Strona 55 - [2] Test Run Method

–145–4) Treatment of Inverter and Compressor TroublesIf the compressor does not work when error codes 4210, 4240, 4310 or 4340 are detected, determine

Strona 56 - (1) Switch function

–146–5) Treatment of Fan Motor Related TroublesCondition Possible Cause Check Method and TreatmentIf there is an open phase condition before the break

Strona 57

–12–INV boardCN3 CN2-1 CN2-2 CN2-3CNVDCCN52CCNFANCNAC2CNR CNRS2 SW1CNCTCN30VCNTHCNL2CNVCC1CNVCC2Power source1 L23 NPower supply (5 V)Power supply1-2 3

Strona 58 - Group setting mode

–147–6) Troubleshooting at breaker trippingCheck items1 Check the breaker capacity.2 Check the a short circuit or grounding in the electricalsystem ot

Strona 59 - CENTRALLY CONTROLLED

–148–7) Individual Parts Failure Judgment Methods.[Caution at replacement of inverter parts]1 The transistor module and INV board should be replaced t

Strona 60 - (Alternative

–149–Model PUHY-400YMF-B, 500YMF-B

Strona 61

–150–8) Compressor Replacement ProcedureWhen replacing a compressor, please proceed by the following procedure.• When replacing the No. 1 compressor (

Strona 62 - 5 CONTROL

–151–(13) Solder the discharge piping, suction piping, volume control valve piping (All but model PUHY-400YMF-B) andprocess piping (All but model PUHY

Strona 63

–152–Belt HeaterNo2. CompressorOil EqualizationPipeBelt Heater Compressor shell temperature sensor(TH10c, PUHY-P-YMF-B only)FasteningFitting 1Flare Nu

Strona 64

–153–Around the No. 2 Compressor (All but model PUHY-400 YMF-B)Insulation + Discharge ThermistorTerminal CoverBelt HeaterMounting fittings 2Discharge

Strona 65

–154–(4) Constant Capacity UnitObserve the following notes when changing the compressor(1) Make sure the main power supply is turned off.If the reason

Strona 66

–155–Process pipePipe joints for Volume Control(PUHN-P-YMF-B only)Terminal coverInsulation + DischargethermistorDischarge pipe jointMounting fittingBe

Strona 67

–156–Check Code Check Content0403 Serial transmission abnoramlity0900 Trial operation1102 Discharge temperature abnormality1111 Low pressure saturatio

Strona 68

–13–FANCON boardCNV CNWCNU CNFC2

Strona 69

–157–Check Code Check Content6607 No ACK abnormality6606 Communications with transmission processor abnormality6608 No response abnormality7100 Total

Strona 70

–158–[2] LED monitor display and Countermeasures Depending on the Check Code Displayed(1) MechanicalChecking code Meaning, detecting method Cause Chec

Strona 71 - [1]-2 PUHY-400·500 YMF-B

–159–Checking code Meaning, detecting method Cause Checking method & Countermeasure111111121113Lowpressuresaturationtempera-turesensorabnor-mality

Strona 72

–160–Checking code Meaning, detecting method Cause Checking method & Countermeasure13011302Low pressureabnormality(Outdoor unit)High pressureabnor

Strona 73

–161–A error is detected in the outlettemperature super heat (TH11,12-Tc) and in the liquid level in theaccumulator as indicated below.1 If the liquid

Strona 74

–162–Checking code Meaning, detecting method Cause Checking method & Countermeasure15051559Suctionpressureabnormality(Variablecapacity unit)Oil ba

Strona 75

–163–Checking code Meaning, detecting method Cause Checking method & Countermeasure2500250225034103Leakage (water)abnormality(Indoor unit)Drain pu

Strona 76

–164–1) Power cord problem(constant capacity unit is discon-nected from the power source)2) Power board fuse (F01, F02) isblown.3) Power board is defe

Strona 77

–165–Checking code Meaning, detecting method Cause Checking method & Countermeasure41164200Fan speedabnormality(motorabnormality)(Indoor unit)VDC

Strona 78

–166–Checking code Meaning, detecting method Cause Checking method & Countermeasure42104220Breaking ofovercurrent(Variablecapacity unit)Bus voltag

Strona 79

–14–RELAY boardCN51C2 CNOUT2 CNRT2CN52F CN52C2 CNCH

Strona 80 - No.1 No.2

–167–Checking code Meaning, detecting method Cause Checking method & Countermeasure42304240Radiator paneloverheatprotection(Variablecapacity unit)

Strona 81

–168–Discharge(TH11)(TH12)LowPressureSatura-tion (TH2)LiquidLevelDetection(TH3)LiquidLevelDetection(TH4)Liquid pipe(TH5)AmbientTempera-ture(TH6)Liquid

Strona 82

–169–Checking code Meaning, detecting method Cause Checking method & Countermeasure520153011When pressure sensor detects1 kg/cm2G (0.098 MPa) or l

Strona 83

–170–(2) Communication/systemCheckingcode66006602Meaning, detecting method Cause Checking method & CountermeasureMultiple address errorTransmissio

Strona 84

–171–Checkingcode66026603Meaning, detecting method Cause Checking method & CountermeasureTransmission processor hard-ware errorTransmission circui

Strona 85

–172–Checkingcode6606Meaning, detecting method Cause Checking method & CountermeasureCommunications with trans-mission processor errorCommunicatio

Strona 86

–173–6607Meaning, detecting methodNo ACK error When no ACK signal is detected in 6 continuous times with 30 second interval by transmission sidecontr

Strona 87

–174–Checkingcode6607(continued)Meaning, detecting methodNo ACK error When no ACK signal is detected in 6 continuous times with 30 second interval by

Strona 88

–175–Checkingcode6607(continued)Meaning, detecting methodNo ACK error When no ACK signal is detected in 6 continuous times with 30 second interval by

Strona 89

–176–Checkingcode6607(continued)Meaning, detecting methodNo ACK error When no ACK signal is detected in 6 continuous times with 30 second interval by

Strona 90

–15–2 Constant capacity unitRearHeat exchangerAccumulator Sub-cool coilAmbient temperature sensorSolenoid valve (SV3, PUHN-P-YMF-B only)Solenoid valve

Strona 91

–177–1) Total capacity of indoor units in thesame refrigerant system exceeds thefollowing:Model Total capacityPUHY-400 520PUHY-500 650PUHY-600 780PUHY

Strona 92 - (A-minute Definitions)

–178–If different units within one system are using different types of refrigerant as shown in table 1 below, the system will notoperate correctly.Tab

Strona 93

–179–[3] LED Monitor Display(1) How to read LED for service monitorBy setting of DIP SW1-1 ~ 1-8 and SW4-2, the unit operating condition can be observ

Strona 94

–180–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD801234567891011121314151617181920000000000010000000000100000000(Also include

Strona 95

–181–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8212223242526272829303132333435363738394041424344454647484950511010100000011

Strona 96

–182–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8525354555657585960616263646566676869707172737475767778798081828384850010110

Strona 97

–183–IC6 Address/Capacity CodeIC7 Address/Capacity CodeIC8 Address/Capacity CodeIC9 Address/Capacity CodeIC10 Address/Capacity CodeIC11 Address/Capaci

Strona 98

–184–0 ~ 9.999↑0000 ~ 9999↑↑↑↑– 99.9 ~ 999.90000 ~ 99990000 ~ 9999↑– 99.9 ~ 999.9↑↑↑↑↑↑↑↑↑↑↑↑↑00101110001010111000011011100011101110000001111000100111

Strona 99

–185–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8142143144145146147148149150151152153154155156157158159160161162163164165166

Strona 100 - (4-minute)

–186–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8172173174175176177178179180181182183184185186187188189190191192193194195196

Strona 101

–16–Controller BoxCONT boardTerminal block TB1powersourceTerminal block TB3transmissionFANCON boardTransformerNoise Filter (NF)Thyristor module(SCRM)M

Strona 102

–187–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8208209210211212213214215216217218219220221222223224225226227228229230231232

Strona 103 - 60 200 2000

–188–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8235236237238239240241242243244245246247248249250251252253254255256257258259

Strona 104

–189–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8011100001011110000100000100010100010001001001000101100100010001010001010101

Strona 105

–190–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8101011001001101100101110110010000111001010011100100101110010110111001000111

Strona 106

–191–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8345346347348349350351352353354355356357358359360361362363364365366367368369

Strona 107

–192–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8381382383384385386387388389390391392393394395396397398399400401402403404405

Strona 108

–193–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8408409410411412413414415416417418419420421422423424425426427428429430431432

Strona 109

–194–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8Variable capacity unit43443543643743843944044144244344444544644744844945045

Strona 110

–195–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8Variable capacity unit47047147247347447547647747847948048148248348448548648

Strona 111

–196–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8Variable capacity unit49649749849950050150250350450550650750850951051100001

Strona 112 - [2] Operation Flow Chart

Contents1 PRECAUTIONS FOR DEVICESTHAT USE R407C REFRIGERANT ... 1[1] Storage of Piping Material ...

Strona 113 - Remove controller

–17–CONT boardSWU2CNTRSWU1CNFC1SW3SW2CNS1M-NETtransmissionCN20Power supply1 N3 L1

Strona 114 - (3) Cooling operation

–197–SV2, 3Only forthePUHN-P-YMF-BNo SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8Relay OutputDisplay 1 (blinkingdisplay)Check D

Strona 115 - During constant

–198–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8Constant capacity unit25262728293031323334353637383940414243444546474849505

Strona 116 - Thermostat ON

–199–No SW1 Item Display Remarks12345678190 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8Constant capacity unit64656667686970717273747576777879808182838485868788899

Strona 117 - Yellow Brown Blue

–200–No SW1 Item Display Remarks12345678910 LD1 LD2 LD3 LD4 LD5 LD6 LD7 LD8Constant capacity unitCOMPOpera-tionSV452C1 21S4 SV1CH2, 310110210310410510

Strona 118

HEAD OFFICE MITSUBISHI DENKI BLDG. MARUNOUCHI TOKYO 100-8310 TELEX J24532 CABLE MELCO TOKYOService Handbook PUHY-400YMF-B, 500YMF-BPUHY-P400YMF-B, P50

Strona 119

–18–BV3TH6TH7TH8TH5CJ1O/S63HSTH11HEX2bHEX1bCJ2CV1SV4SV1CP1TH4TH3CP4BV2BV1TH12Comp2Comp1HEX2aHEX1aCV2SAMACP3aSV6SCCLEV163H163H221S4a21S4bSV5bSV22SV32ST

Strona 120

–19–2 PUHY-400·500YMF-BCP1ST6SV1SLEVCP4No.1Comp.TH8HEX2aTH5SV5bHEX1aTH6HEX2bHEX1b21S4b21S4aCJ163HSST5SV4SV6TH1163H1CV1O/SCJ2BV1ST1MASATH2CP2ST2BV2BV3S

Strona 121

–20–3 PUHY-P600·650·700·750YSMF-BDistributer(Gas)Indoor unitOil balancepipeBV3TH6TH7TH8TH5CJ1O/S63HSTH11HEX2bHEX1bCJ2CV1SV4SV1CP1TH4TH3CP4BV2BV1TH12Co

Strona 122

–21–21S4bHEX1bTH6TH10bHEX2b21S4aCJ163HSST5SV4SV6TH10aO/SST6CP1SV1HEX1aHEX2aSV5bTH5CV163H1TH11Comp1Comp2TH8ST10CP4SLEVTH4ST4ST8CJ363H2CV2CP3aTH12SV22

Strona 123 - 1234567 8910

–22–40LW-FD. Indoor unitCassette ceilingCeiling concealedWall mountedCeiling suspendedFloor standingExposed ConcealedPLFY-PPLFY-P PEFY-P PKFY-P PCFY-P

Strona 124

–23–

Strona 125

–24–*3:NF is in the back of the Inverter Controller Box. (Refer to the <Unit Internal layout>.)642531642531BlackWhiteRedBlackWhiteRedCH11Fan mo

Strona 126

–25–FLAG3FLAG2FLAG1FLAG5FLAG6FLAG7<LED display>FLAG4FLAG8LED1TH7❇3PUHY-P400YMF-B -(P)500YMF-BPUHY-400YMF-BSV22MC263H2TH12SV5b21S4bSV6SV4SV1TH12

Strona 127 - Caution:

–26–2 PUHN-(P)200·250YMF-BModel 200: 24AModel 250: 27A*1<Difference of appliance>*1Appliance PUHN-P200·250YMF-BPUHN- 200·250YMF-BL2L1L3PE5GKGKGK

Strona 128 - PUHY-(P) 400·500 YMF-B

Safety precautionsBefore installation and electric works Before installing the unit, make sure you read allthe “Safety precautions”.s The “Safety prec

Strona 129

–27–Discharge (TH11/TH12)Heat exchanger outlet (TH5)InletAccumulatorOutletSuction (Comp) (No.1/No.2)Low pressure saturationtemperature (TH2)Upper (TH4

Strona 130

–28–Discharge (TH11/TH12)Heat exchanger outlet (TH5)AccumulatorInletOutletSuction (Comp)Low pressure saturationtemperature (TH2)Liquid levelUpper (TH4

Strona 131 - Pressure→

–29–Discharge (TH11/TH12)Heat exchanger outlet (TH5)AccumulatorInletOutletSuction (Comp)Low pressure saturationtemperature (TH2)Liquid levelUpper (TH4

Strona 132 - 7 TROUBLESHOOTING

–30–27.0/19.5 27.0/19.535.0/24.0 35.0/24.055555555 5522.4 28.928.2/26.8/25.8 34.2/32.5/31.3164 17934420.0/4.4 20.0/4.3(1.96/0.43) (1.96/0.42)90/95 95/

Strona 133 - Solenoid Valve

–31–VariablecapacityunitConstantcapacityunitIndoor unitOutdoor unitItemsAmbient temp.Indoor unitPipingConditionIndoorOutdoorQuantityQuantity in operat

Strona 134

–32–VariablecapacityunitConstantcapacityunitIndoor unitOutdoor unitItemsAmbient temp.Indoor unitPipingConditionIndoorOutdoorQuantityQuantity in operat

Strona 135 - Outdoor Unit Fan

–33–Discharge (TH11/TH12)Heat exchanger inlet (TH5)InletAccumulatorOutletSuction (Comp) (No.1/No.2)Low pressure saturationtemperature (TH2)Upper (TH4)

Strona 136 - Outdoor LEV

–34–Discharge (TH11/TH12)Heat exchanger outlet (TH5)AccumulatorInletOutletSuction (Comp)Low pressure saturationtemperature (TH2)Liquid levelUpper (TH4

Strona 137

–35–Discharge (TH11/TH12)Heat exchanger outlet (TH5)AccumulatorInletOutletSuction (Comp)Low pressure saturationtemperature (TH2)Liquid levelUpper (TH4

Strona 138 - <LEV1, SLEV>

–36–21.0/- 21.0/-7.0/6.0 7.0/6.055555555 5522.4 28.726.0/24.7/23.8 32.2/30.6/29.50012218.0/3.6 18.0/3.2(1.77/0.35) (1.77/0.31)85/90 85/9079– 4 – 5– 4

Strona 139

–1–11111 PRECAUTIONS FOR DEVICES THAT USE R407C REFRIGERANTCautionDo not use the existing refrigerant piping.• The old refrigerant and refrigerator oi

Strona 140

–37–VariablecapacityunitConstantcapacityunitIndoor unitOutdoor unitItemsAmbient temp.Indoor unitPipingConditionIndoorOutdoorQuantityQuantity in operat

Strona 141 - AK2 AK2 AK2

–38–VariablecapacityunitConstantcapacityunitIndoor unitOutdoor unitItemsAmbient temp.Indoor unitPipingConditionIndoorOutdoorQuantityQuantity in operat

Strona 142 - Faulty outdoor unit

–39–Function According to Switch Operation Switch Set TimingWhen Off When On When Off When OnSWU 1 ~ 2SW11 ~ 8Refer to LED monitor display on the outd

Strona 143 - Same symptom for all

–40–2 Constant Capacity UnitFunction According to Switch Operation Switch Set TimingWhen Off When On When Off When OnSWU 1 ~ 2SW212345678910SW31234567

Strona 144

–41–-Centralized control notconnected.Storing of refrigerationsystem connectioninformation.Store IC•OC error history.Ordinary control--Ordinary contro

Strona 145

–42–2 Constant Capacity UnitFunction According to Switch Operation Switch Set TimingWhen Off When On When Off When OnSWU 1 ~ 2SW212345678910SW31234567

Strona 146

–43–(2) Indoor unitDIP SW1, 3Note 1: The shaded part indicates the setting at factory shipment. (For the SW not being shaded, refer to th

Strona 147

–44–Ceiling height3 3.5 m2 2.8 m1 2.3 mSetting of DIP SW4 Setting of DIP SW51234ON OFF ON OFF––––ON OFF ON OFFOFF OFF OFF ONON OFF OFF ONOFF ON OFF O

Strona 148

–45–33333 TEST RUN[1] Before Test Run(1) Check points before test run1 Neither refrigerant leak nor loose power source/ transmission lines should be f

Strona 149

–46–(3) Check points for test run when mounting options(4) Attention for mounting drain water lifting-up mechanismBuilt-in optional parts Content of t

Strona 150

–2–[1] Storage of Piping Material(1) Storage locationStore the pipes to be used indoors. (Warehouse at site or owner’s warehouse)Storing them outdoors

Strona 152 - Model PUHY-400YMF-B, 500YMF-B

–48–(5) Check points for system structureIn the case of the PUHY-(P) 400·500 YMF-BCheck points from installation work to test run.Classification Porti

Strona 153

–49–Classification Portion Check item TroubleTransmissionlineSystem setBefore startingLimitation of transmission line length followed? Forexample, 200

Strona 154

–50–PowersourceforoutdoorunitSwitchSwitchMAIN boardOutdoor unit21161234516215782In the case of the PUHY-(P) 600·650·700·750 YSMF-BCheck points from in

Strona 155

–51–Classification Portion Check item TroubleTransmissionlineSystem setBefore startingLimitation of transmission line length followed? Forexample, 200

Strona 156

–52–[2] Test Run MethodNote) 1. If check code is displayed on remote controller or remote controller does not operate normally.2. Test run automatical

Strona 157

–53–44444 GROUPING REGISTRATION OF INDOOR UNITS WITH REMOTE CONTROLLER(1) Switch function• The switch operation to register with the remote controller

Strona 158

–54–(2) Attribute display of unit• At the group registration and the confirmation/deletion of registration/connection information, the type (attribute

Strona 159 - Inverter error detail *1

–55–(3) Group registration of indoor unit1) Registration method• Group registration of indoor unit ... 1The indoor unit to be contro

Strona 160

–56–2) Method of retrieval/confirmation• Retrieval/confirmation of group registration information on indoor unit... 2The address of the i

Strona 161 - (1) Mechanical

–3–[2] Piping MachiningUse ester oil, ether oil or alkylbenzene (small amount) as the refrigerator oil to coat flares and flange connections.Use only

Strona 162

–57–3) Method of deletion• Deletion of group registration information of indoor unit ... 4[Operation procedure]1 With the remote control

Strona 163

–58–4) Deletion of information on address not existing• Deletion of information on address not existing ... 5This operation is to be con

Strona 164

–59–55555 CONTROL[1] Control of Outdoor Unit[1]- 1 PUHY-P400·500 YMF-B(1) Initial processing• When turning on power source, initial processing of micr

Strona 165

–60–• The operating temperature is 124°C (No. 1 compressor) or 115°C (No. 2 compressor).4) Compressor frequency control1 Ordinary controlThe ordinary

Strona 166

–61–ItemAt compressor is startedCompressor stopped during cool-ing or heating modeAfter operation has been stoppedDuring defrosting ((*1) in Fig below

Strona 167

–62–(5) Oil return control (Electronic expansion valve (SLEV))• The amount of opening of the oil-return LEV (SLEV) is determined as follows: in coolin

Strona 168

–63–5) Change in number of operating indoor units while defrosting• If the number of indoor units changes while the outdoor unit is defrosting, the de

Strona 169

–64–(10) Refrigerant recovery controlRefrigerant recovery is conducted to prevent refrigerant from accumulating in the stopped unit (fan unit), the un

Strona 170

–65–(12) Control at initial starting• When the ambient temperature is low (5°C or less in cooling and – 5°C or less in heating), initial starting will

Strona 171

–66–<Initial start control timing chart>Note 1: If the frequency of No. 1 compressor is above the specified level at the end of Step 2, the mode

Strona 172

–4–[3] Necessary Apparatus and Materials and Notes on Their HandlingThe following tools should be marked as dedicated tools for R407C.<<Comparis

Strona 173 - (2) Communication/system

–67–(13) Operation Mode1) Operating modes of the indoor unitThe following five modes can be set by the remote control.1 Cooling mode2 Heating mode3 Dr

Strona 174 - Transmission line

–68–[1]-2 PUHY-400·500 YMF-B(1) Initial processing• When turning on power source, initial processing of microcomputer is given top priority.• During i

Strona 175

–69–• The operating temperature is 124°C.4) Compressor frequency control1 Ordinary controlThe ordinary control is performed after the following times

Strona 176

–70–ItemAt compressor is startedCompressor stopped during cool-ing or heating modeAfter operation has been stoppedDuring defrosting ((*1) in Fig below

Strona 177

–71–(5) Oil return control (Electronic expansion valve (SLEV))• The amount of opening of the oil-return LEV (SLEV) is determined as follows: in coolin

Strona 178

–72–5) Change in number of operating indoor units while defrosting• If the number of indoor units changes while the outdoor unit is defrosting, the de

Strona 179

–73–(10) Refrigerant recovery controlRefrigerant recovery is conducted to prevent refrigerant from accumulating in the stopped unit (fan unit), the un

Strona 180 - (3) System error

–74–(12) Control at initial starting• When the ambient temperature is low (5°C or less in cooling and – 5°C or less in heating), initial starting will

Strona 181

–75–<Initial start control timing chart>Note 1: If the frequency of No. 1 compressor is above the specified level at the end of Step 2, the mode

Strona 182 - [3] LED Monitor Display

–76–(13) Operation Mode1) Operating modes of the indoor unitThe following five modes can be set by the remote control.1 Cooling mode2 Heating mode3 Dr

Strona 183 - Detection

–5–[4] BrazingNo changes from the conventional method, but special care is required so that foreign matter (ie. oxide scale, water, dirt,etc.) does no

Strona 184

–77–[1]- 3 PUHY-P600·650·700·750 YSMF-B(1) Initial processing• When turning on power source, initial processing of microcomputer is given top priority

Strona 185

–78–2 Switching No. 3 compressor from operation to stoppingWhen the required performance is exceeded with the No. 1 and No. 2 variable capacity unit c

Strona 186

–79–(4) Bypass - capacity controlThe solenoid valves have bypass valves (SV1, SV4 and SV6) that allow bypassing of the high pressure and lowpressure s

Strona 187

–80–130°C(No. 1 compressor)115°C(No. 2 compressor)• Td >SV1ON OFFON for 4 minutesONON for 3 minutesONON during oil recovery operation aftercontinuo

Strona 188

–81–ItemAt compressor is startedAfter thermostat reset or 3minutes after startupCompressor stopped duringcooling or heating modeAfter operation has be

Strona 189

–82–(5) Oil return control (Electronic expansion valve (SLEV); Variable Capacity Unit only)• The amount of opening of the oil-return LEV (SLEV) is det

Strona 190

–83–5) Change in number of operating indoor units while defrosting• If the number of indoor units changes while the outdoor unit is defrosting, the de

Strona 191

–84–(10) Liquid Distribution Control (electronic expansion valve (LEV2) constant capacity unit only)• Liquid distribution control refers to the proces

Strona 192

–85–(11) Liquid Refrigerant Correction ControlThe liquid refrigerant correction control adjusts the liquid refrigerant amounts between both accumulato

Strona 193

–86–(12) Refrigerant recovery controlRefrigerant recovery is conducted to prevent refrigerant from accumulating in the stopped unit (fan unit), the un

Strona 194

–6–[5] Airtightness TestNo changes from the conventional method. Note that a refrigerant leakage detector for R22 cannot detect R407Cleakage.Halide to

Strona 195

–87–(14) Control at initial starting• When the ambient temperature is low (5°C or less in cooling and – 5°C or less in heating), initial starting will

Strona 196

–88–<Initial Start Control Timingchart>For steps 1 - 3Note 1: If the frequency of No. 1 compressor is above the specified level at the end of St

Strona 197

–89–For steps 4 - 6OperationFrequency Level (Hz)–217 (For variable capacityunit model 500)183 (For variable capacityunit model 400)100100Less than 100

Strona 198

–90–Note 1: If Step 4 is interrupted (compressor stopped by thermostat OFF or regular stop), Step 4 will be redone atrestart.Note 2: If Step 5 is inte

Strona 199

–91–(17) Emergency response operating modeThe emergency operation mode is a mode in which the unit is run in an emergency to respond to the trouble wh

Strona 200

–92–2) Terminating Emergency Response Operation Mode(Termination Conditions)When one of the following conditions is met, emergency operation mode is t

Strona 201

–93–[1]-4 PUHY-600·650·700·750 YSMF-B(1) Initial processing• When turning on power source, initial processing of microcomputer is given top priority.•

Strona 202

–94–2 Switching No. 3 compressor from operation to stoppingWhen the required performance is exceeded with the No. 1 and No. 2 variable capacity unit c

Strona 203

–95–(4) Bypass - capacity controlThe solenoid valves have bypass valves (SV1, SV4 and SV6) that allow bypassing of the high pressure and lowpressure s

Strona 204 - PUHY-P400YMF-B, P500YMF-B

–96–ItemAt compressor is startedCompressor stopped during cool-ing or heating modeAfter operation has been stoppedDuring defrosting ((*1) in Fig below

Komentarze do niniejszej Instrukcji

Brak uwag