SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ····································2
2. PART NAMES AND FUNCTIONS······················5
3. SPECIFICATION·················································6
4. NOISE CRITERIA CURVES·······························8
5. OUTLINES AND DIMENSIONS ·························9
6. WIRING DIAGRAM ··········································10
7. REFRIGERANT SYSTEM DIAGRAM ··············12
8. PERFORMANCE CURVES······························15
9. SERVICE FUNCTIONS ····································25
10. TROUBLESHOOTING······································25
11. DISASSEMBLY INSTRUCTIONS·····················36
12. PARTS LIST······················································40
13. RoHS PARTS LIST···········································46
Models
MUH-GA50VB -
MUH-GA50VB -
MUH-GA60VB -
MUH-GA80VB -
E1
E1
E2
E1
SPLIT-TYPE AIR CONDITIONERS
MUH-GA50VB
NOTE:
This service manual describes technical data of outdoor units.
RoHS compliant products have <G> mark on the spec name plate.
For servicing of RoHS compliant products, refer to the RoHS Parts List.
HFC
utilized
R410A
OUTDOOR UNIT
No. OB368
REVISED EDITION-C
Please void OB368 REVISED EDITION-B.
Revision:C
• The fan guard for MUH-GA60VB- and
MUH-GA80VB- has been changed.
E1
E1
Indoor unit service manual
MSH-GAVB Series (OB367)
OB368B-1.qxp 10.5.25 9:14 AM Page 1
Przeglądanie stron 0
1 2 3 4 5 6 ... 51 52

Podsumowanie treści

Strona 1 - MUH-GA80VB

SERVICE MANUALCONTENTS1. TECHNICAL CHANGES ····································2 2. PART NAMES AND FUNCTIONS······················53. SPECIFICATION···

Strona 2 - TECHNICAL CHANGES

10WIRING DIAGRAM6MUH-GA60VB DEICERP.C. BOARDBLUX52X52NOCOMTAB52BLU52CA2A1T61BLKWHTREDBRNTB271CN730BLKWHTCIRCUIT BREAKER CN721352C4REDC2ORNDSAR

Strona 3

11DEICERP.C. BOARDT61YLWBLKWHTREDBRNTB271CN730YLWBLKWHTCIRCUIT BREAKER CN721152C2CZWHTWHTREDC2ORNA1 A2BLU52CDSARTO INDOOR UNIT CONNECTING 12VW

Strona 4 - 2.Refrigerant piping

12REFRIGERANT SYSTEM DIAGRAM7MufflerMUH-GA50VB -E1Refrigerant pipe [12.7(with heat insulator)Flared connectionFlared connectionRefrigerant pipe [6.35(

Strona 5 - PART NAMES AND FUNCTIONS

13MUH-GA80VB Unit:mmOutdoorheatexchangerFlared connectionDefrostthermistorRT61DischargetemperaturethermistorRT62Flared connectionStop valveStop valv

Strona 6 - SPECIFICATION

14ModelMUH-GA50VB Refrigerant piping length (one way)Outdoor unit precharged1,80015m16020m26025m3607m010m60ADDITIONAL REFRIGERANT CHARGE(R410A : g)Cal

Strona 7

15PERFORMANCE CURVES811.610.57.58.59.512.815.69.812.611.214.117.217.413.912.410.815.619.2MUH-GA50VBMSH-GA60VBMSH-GA50VBMUH-GA60VBMSH-GA80VBMUH-GA80VBT

Strona 8 - NOISE CRITERIA CURVES

1626.624.522.520.418.416.314.312.336.834.031.128.325.522.619.817.038.435.532.529.626.623.620.717.7MUH-GA50VBMSH-GA60VBMSH-GA50VBMUH-GA60VBMSH-GA80VBMU

Strona 9 - OUTLINES AND DIMENSIONS

17HEAT operationCondition indoor:Dry bulb temperature 20.0°CWet bulb temperature 14.5°COutdoor:Dry bulb temperature 7,15,20°CWet bulb temperature 6,12

Strona 10 - WIRING DIAGRAM

18MSH-GA50VB : MUH-GA50VB (230V)21 18 5.88 2.76 0.47 1424 5.63 2.64 0.47 1495 5.40 2.54 0.47 1566 5.20 2.44 0.47 163821 20 6.13 2.14 0.35 1495 5.88 2

Strona 11 - 3.Symbols below indicate

1921 18 4.90 2.30 0.47 1744 4.50 2.12 0.47 1851 4.33 2.03 0.47 188721 20 5.15 1.80 0.35 1816 4.80 1.68 0.35 1905 4.63 1.62 0.35 195822 18 4.90 2.50 0.

Strona 12 - REFRIGERANT SYSTEM DIAGRAM

2RefrigeratingoilRefrigerantNew refrigerantR410AHFC-32: HFC-125 (50%:50%)Pseudo-azeotropic refrigerantNot includedA1/A172.6-51.41.55764Non combustible

Strona 13 - MUH-GA60VB

20MSH-GA60VB : MUH-GA60VB (230V)21 18 7.40 3.41 0.46 1928 7.09 3.26 0.46 2024 6.80 3.13 0.46 2121 6.55 3.01 0.46 221721 20 7.72 2.62 0.34 2024 7.40 2

Strona 14 - MAX. HEIGHT DIFFERENCE

2121 18 6.17 2.84 0.46 2362 5.67 2.61 0.46 2506 5.45 2.51 0.46 255521 20 6.49 2.21 0.34 2458 6.05 2.06 0.34 2579 5.83 1.98 0.34 265122 18 6.17 3.09 0.

Strona 15 - PERFORMANCE CURVES

2221 18 9.99 4.39 0.44 2608 9.56 4.21 0.44 2738 9.18 4.04 0.44 2869 8.84 3.89 0.44 299921 20 10.41 3.33 0.32 2738 9.99 3.20 0.32 2901 9.69 3.10 0.32 2

Strona 16 - (kgf/F[Gauge])(MPa[Gauge])

2321 18 8.33 3.67 0.44 3195 7.65 3.37 0.44 3390 7.35 3.24 0.44 345621 20 8.76 2.80 0.32 3325 8.16 2.61 0.32 3488 7.86 2.52 0.32 358622 18 8.33 4.00 0.

Strona 17

24OUTDOOR WB(:)INDOOR-10 -5 0 5 10 15 20DB(:)Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUT Q INPUTCAPACITY : 5.2(kW)INPUT : 1610(W)1521263.283.122

Strona 18

25SERVICE FUNCTIONS99-1. COMPULSORY DEFROSTING MODE FOR SERVICEBy short circuit of the connector JPDS and JPSG(MUH-GA50VB)/ JPG1 and R871(MUH-GA60/GA8

Strona 19

26StartIndoor unit operates.Outdoor unit doesn't operate.Indoor unit doesn't receive the signal from remote controller.Indoor unit operates

Strona 20

2710-3. TROUBLE CRITERION OF MAIN PARTSMUH-GA50VB MUH-GA60VB MUH-GA80VBPart name FigureCheck method and criterionMeasure the resistance between the

Strona 21

28AACheck of outdoor unitCompressor and/or outdoor fan motor doesn’t operate.Ye sCompressor doesn't operate.Ye sYe sIs there 230V AC between 3 on

Strona 22

29Is there 230V AC to between L-N on the outdoor terminal block?NoCheck the outdoor power supply and connection of wiring.Ye sCompressor does not oper

Strona 23

3NOTE : The unit of pressure has been changed to MPa on the international system of units(SI unit system).The conversion factor is: 1(MPa [Gauge]) =10

Strona 24

30After 30 seconds, does compressor stop?NoYesIs there 230V AC between A1-A2 on the compressor contactor (52C)?Replace the deicer P.C. board.Yes1 Turn

Strona 25 - TROUBLESHOOTING

31How to check mis-wiringD1. Turn OFF the power supply (indoor/ outdoor unit) and disconnect indoor/outdoor connecting wire on indoor side.2. Short-ci

Strona 26

32Check of LEV (Expansion valve)EReplace the LEV.With remote controller set toward the indoor unit, press OPERATE/ STOP (ON/ OFF) button and confirm o

Strona 27 - :INNER PROTECTOR

33Check of outdoor thermistorMeasure resistance between CN 661 1 and 2.Measure resistance between CN 662 3 and 4.NoYe sReplace the thermistor.Measure

Strona 28 - Check of outdoor unit

34MUH-GA50VBOutdoor deicer P.C. boardCN711Outdoor fan motor 230V ACCN721R.V. coil230V ACF61Fuse2A/250V}}CN661 1-2Defrost thermistor RT61 (Refer to 10-

Strona 29

35MUH-GA60VB MUH-GA80VB Outdoor deicer P.C. boardVaristor(NR62)Fuse 3.15A / 250VDefrostintervaltime shortpin(JPG1,R871)(Refer to9-1.)}12V DCJumper

Strona 30 - Check of R.V. coil

36DISASSEMBLY INSTRUCTIONS11OPERATING PROCEDUREPHOTOS1. Removing the cabinet(1) Remove the screws of the cabinet.(2) Hold the down of the cabinet on t

Strona 31 - How to check mis-wiring

37OPERATING PROCEDUREPHOTOSPhoto 5Terminal coverCompressorDischargepipeSuctionpipeCompressor set nutsPhoto 4PropellerSet screws of the outdoor fan mo

Strona 32

3811-2. MUH-GA60VB MUH-GA80VBOUTDOOR UNITNOTE : These photos are MUH-GA80VB.MUH-GA60VB is almost the same as MUH-GA80VB.OPERATING PROCEDUREPHOTOS1.Re

Strona 33 - Check of outdoor thermistor

39Photo 6Suction pipeDischarge pipeTerminal coverOPERATING PROCEDUREPHOTOS3. Removing the propeller and the outdoor fan motor(1) Remove the cabinet. (

Strona 34

4R410APipe diametermm6.359.5212.715.8817222629Dimension of flare nutR22172224272 Flaring work and flare nutFlaring work for R410A pipe differs from th

Strona 35 - Outdoor deicer P.C. board

40PARTS LIST (non-RoHS compliant)121204131211109876532MUH-GA50VB 12-1. OUTDOOR UNIT STRUCTURAL PARTS,ELECTRICAL PARTS AND FUNCTIONAL PARTS211416181915

Strona 36 - DISASSEMBLY INSTRUCTIONS

41Symbolin WiringDiagramQ'ty/unitMUH-GA50VB -RemarksPart No. Part NameE1E02 817 233E02 817 232E02 817 521E02 643 630E02 141 501E02 139 515E02 07

Strona 37 - OPERATING PROCEDURE

42MUH-GA60VB12-3. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS323161211513 142456789101117181920212224252627PARTS LIST (non-Ro

Strona 38 - OUTDOOR UNIT

43MUH-GA60VB 12-3. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTSMUH-GA60VB - E1Symbolin WiringDiagramQ'ty/unitRemarksPar

Strona 39

44MUH-GA80VB12-5. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS424171311614 152567891011121819202122232526272832PARTS LIST (non

Strona 40 - 12-2. ACCESSORY

45MUH-GA80VB12-5. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTSMUH-GA80VB - E1Symbolin WiringDiagramQ'ty/unitRemarksPart

Strona 41

46131204131211109876532MUH-GA50VB 13-1. OUTDOOR UNIT STRUCTURAL PARTS,ELECTRICAL PARTS AND FUNCTIONAL PARTS21141618191517RoHS PARTS LIST (RoHS complia

Strona 42 - 12-4. ACCESSORY

47Symbolin WiringDiagramQ'ty/unitMUH-GA50VBRemarksPart No. Part NameE1-E2-E02 817 233E02 A27 233E02 817 232E02 817 521E02 643 630E02 B35 630E02 1

Strona 43

48RoHS PARTS LIST (RoHS compliant)MUH-GA60VB13-3. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS323161211513 1424567891011171819

Strona 44 - 12-6. ACCESSORY

49RoHS PARTS LIST (RoHS compliant)MUH-GA60VB 13-3. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTSMUH-GA60VB - E1Symbolin Wirin

Strona 45

5PART NAMES AND FUNCTIONS2Drainage hosePipingAir inletAir inletAir outletDrain outlet(back and side)Air outlet(back and side)ACCESSORIESMUH-GA50VB12Dr

Strona 46 - 13-2. ACCESSORY

50RoHS PARTS LIST (RoHS compliant)MUH-GA80VB13-5. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTS424171311614 1525678910111218192

Strona 47

51RoHS PARTS LIST (RoHS compliant)MUH-GA80VB13-5. OUTDOOR UNIT STRUCTURAL PARTS, ELECTRICAL PARTS AND FUNCTIONAL PARTSMUH-GA80VB - E1Symbolin Wiring

Strona 48 - 13-4. ACCESSORY

New publication, effective Jun. 2010Specifications subject to change without notice.CCCopyright 2004 MITSUBISHI ELECTRIC ENGINEERING CO.,LTDDistribute

Strona 49

6WHT-BLK 71.2BLK-RED 89.3WHT-BLK 79.5BLK-RED 83.0Outdoor modelFunctionPower supplyCapacityDehumidificationAir flow(High) Power outletRunning currentPo

Strona 50 - 13-6. ACCESSORY

7Outdoor modelFunctionPower supplyCapacityDehumidificationAir flow(High/Low)Power outletRunning currentPower inputPower factorStarting currentCompress

Strona 51

8NOISE CRITERIA CURVES490807060504030201063 125 250 500 1000 2000 4000 8000NC-60NC-50NC-40NC-30NC-20NC-70BAND CENTER FREQUENCIES, HzTest conditions,

Strona 52

9MUH-GA60VB MUH-GA80VBOUTLINES AND DIMENSIONS5Unit: mmMUH-GA50VB100mm or more100mm or more100mm or more350mm or more500mm or moreREQUIRED SPACEDrain